ST-80 SIX STREAM SEQUENCER WITH DISPLAY, ALARM & MODBUS® MASTER / SLAVE

  • Controls sequencing of up to 6 input streams to gas or liquid process analyzers. 5 amp Form C relays are provided for switching stream sample valves
  • Large LED readout displays analyzer data for the selected stream including stream #, engineering units and value. Small LCD readout provides operator interface and diagnostics
  • 3 independent alarm levels per stream with 5 amp Form C relay outputs. Relay Acknowledge feature allows silencing of external audible devices during existing alarm conditions
  • Standard SPDT common alarm relays for Horn, HIGH, WARN & FAULT. Optional discrete stream alarm relays also available
  • Options such as 4-20mA outputs, discrete alarm relays and others are supported via an I2C expansion bus
  • Cal Mode offers pushbutton zero / span analyzer calibration from the ST-80 front panel. Authorization Mode allows locking of critical configuration variables
  • Dual Modbus serial ports for simultaneous master / slave operation
  • Magnetic keypad available for non-intrusive operation in potentially hazardous locations
  • NEMA 4X, Explosion-Proof, surface mount, panel and rack mount packaging options available


The R. C. Systems Co., Inc. Model ST-80 Six Stream Sequencer is designed to time share a process gas, or liquid analyzer, between as many as 6 sample streams. Integral timers determine how long any stream is being sent to the analyzer. A large LED display, and 3 adjustable alarm levels for each stream are standard. Relay outputs allow control of stream valve manifolds, alarm beacons, horns and other events.

Input signal from the analyzer is typically accepted by the analog input. Six 4-20mA outputs utilizes track / hold features to provide discrete output signals for each stream. A seventh 4-20mA output indicates stream ID of the selected stream.

The ST-80 is easy to configure and user friendly. Large LED characters indicate stream #, engineering units and values. A 2 x 16 LCD readout provides operator interface and diagnostic functions. Measurement ranges in engineering units, adjustable alarm set-points, dual serial interfaces and many other features combine to allow the ST-80 satisfy the needs of many difficult applications. It is often applied when continuous stream analysis is not required and it is desirable to share the analyzer in order to reduce procurement and installation costs.

A RS-485 Modbus slave port allows up to 128 ST-80's to be multidropped onto a single data highway for interrogation by another Modbus master. ST-80’s may also be cascaded by connecting one unit’s master port to another’s slave port.

ST-80 options such as discrete alarm relays per channel, 4-20mA I/O, direct sensor input conditioning and others are added by connecting to the economical I2C expansion bus. Familiar “telephone style” cables and connectors interface to this bus. This method allows versatile system configuration of options satisfying the most unusual user applications.

Nonvolatile memory retains all configuration data indefinitely.





8621 Hwy. 6 Hitchcock , TX   77563 Tel: 409-986-9800 Fax: 409-986-9880
Products | Technical Info | News | Downloads | Languages | Representatives | Contact Us | Home
Copyright 2010 RC Systems Co. Inc. All rights reserved.